Features
Protect life and property from faulty appliancesBattery operatedPASS / FAIL resultColor status back light10 mA & 30 mA RCD test(Isolation transformer built in)Memory function up to 999 dataPrinter outputComplies to AS / NZS 3760This instrument is suitable for performing tests as required by the following standards. AS/NZS 3760 In-service safety inspection and testing of electrical equipme
TEST FUNCTION
TEST FUNCTION
Tests of contents
Class Ⅰ Test
• Protective conductor resistance
(Test current 200mA DC nominal)
• Insulation resistance test (250V or 500V)
• Leakage current test (100-253V/50Hz)
• Load current test (100-253V/50Hz
Class Ⅱ Test
• Protective conductor resistance
(Test current 200mA DC nominal)
• Insulation resistance test
(between Line/Neutral-Earth short, Line/Neutral)
• Leakage current test (100-253V/50Hz)
• Polarity test
RCD Test
• RCD test (10mA/30mA)
Mains voltage indlcation
Display range
30V-270V
Accuracy
±5V
Protective conductor resistance test
Measuring range
0.00-20.00Ω
Open circuit voltage
5V±0.4V DC
Measuring current
200mA DC(nominal value)
Accuracy
±3%rdg±5dgt
Insulation resistance test
Rated volatge
250V - 500V
Measuring range
0.00-20.00MΩ
No-load voltage
250V DC +20%,-0% - 500V DC +20%,-0%
Short circuit current
1.5mA DC or less
Accuracy
±2%rdg±3dgt
Load current/Leakage current test
Item
Load current - Leakage current
Mains voltage range
100-253V/50Hz
Measuring range
0.10-10.00A rms 0.10-20.00mA rms
Accuracy
±10%rdg±5dgt ±3%rdg±5dgt
RCD test
Rated voltage
230V -15% – +10%/50Hz
Rated current
10mA/30mA
Function
× 1 × 5
Test duration
0.0ms-500.0ms 0.0ms-40.0ms
RCD test
Rated voltage
230V -15% – +10%/50Hz
Rated current
10mA/30mA
Function
× 1/ × 5
Test duration
0.0ms-500.0ms 0.0ms-40.0ms
Operating time accuracy
±2ms(≦40ms),±8ms(>40ms)
General
Power source
LR6(AA)(1.5V) × 6
Applicable Standards
IEC/EN61010-1 CAT II 300V, IEC/EN61010-2-030,
IEC/EN61010-031, EN61326-2-2, AS/NZ3760
Dimentions / Weight
261(L) × 104(W) × 57(D)mm / Approx. 930g(including batteries)
Included Accessories
7277(Mains lead),
7129A(Test lead with Alligator clip),
7161A(Flat test prod),
7276(Adaptor for Extension cord),
9193(Carrying case),
8928(Fuse[10A/250V]),
9121(Shoulder strap),
Buckle, LR6(AA) x 6, Instruction manual
Optional Accessories
8263-USB(USB cable with “KEW Report(software)”),
7275(Printer cable:Mini Din 6pin-D-sub 9pin),
7248(Test lead with Alligator clip and Flat test probe)