Features
3 channel inputs for the simultaneous recording of Leakage Current and Load Current Large capacity for storing 60,000 data pointsLowpass Filter will filter out the harmonicsLED flickers when the preset current value is exceededCALL:Confirmation of recorded dataSelection of One-time mode or Endless modeNon Volatile MemoryBattery power indicatorThe userfriendly PC software “KEW LOG Soft 2” is suppliedContinuous measuring time:Approx. 10 days (Alkaline Battery)
Product Description
3 channel inputs for the simultaneous recording of Leakage Current, Load Current and VoltageLarge Capacity for storing 60,000 data points :- 60,000 data points can be recorded when 1ch is used, and when all the three channels are used, 20,000 data points per channel can be recordedLowpass Filter will filter out the harmonics (Cutoff Frequency=Approx. 160Hz)LED flickers when the preset current value is exceededCALL: Confirmation of recorded data :- The following can be displayed: number of recorded data points, (max+ min+ peak) value for each channel complete with time/date information in the Normal recording mode. (Detected values (i.e. when values are outside preset limits ) can be displayed in other recording modes). RECALL: The last 10 recorded data points including time/date can be recalled on the logger displaySelection of One-time mode or Endless mode :- One-time on: Recording will stop when memory is used up. One-time off: Overwrite the old data, and store the latest dataNon Volatile Memory :- Recorded data will be retained even if the batteries are exhausted or replaced due to the presence of a nonvolatile memory (guaranteed for 10 years)Battery power indicator :- ndicates battery voltage in 4-levels (It is possible to use the logger for a further approx. 24 hours even after the warming symbol is flashing)The userfriendly PC software “KEW LOG Soft 2” is supplied :- Supplied with the user friendly software “KEW LOG Soft 2”. This permits editing, analysis and graphical display of data. The recorded data is downloadable onto a PC via USB cable.Continuous measuring time: Approx. 10 days (Alkaline Battery)
Normal Recording Mode (AC 50/60Hz, Sine wave, Input: 10% or more of the range at CH1)
Range
RMS Accuracy
100.0mA
±2.0%rdg±0.9%f.s.+ Accuracy of Senso
Other ranges
±1.5%rdg±0.7%f.s.+ Accuracy of Sensor
Crest Factor
2.5 or less: RMS accuracy (sine) + 2%rdg + 1%f.s.
Max, Min and Instant Peak values in Normal Recording mode are just reference values: their accuracies aren’t guaranteed.
Trigger Recording Mode (AC 50/60Hz sine wave)
Range
Accuracy
100.0mA
±3.5%rdg±2.2%f.s.+ Accuracy of Sensor
Other ranges
±3.0%rdg±2.0%f.s.+ Accuracy of Sensor
Capture Recording Mode
Range
Accuracy
100.0mA
100.0mA
Other ranges
±2.5%rdg±1.5%f.s.+ Accuracy of Sensor
Recording mode
Normal, Trigger, Capture
Operating system
Successive Approximation
(CH1 single synchronized sampling)
Rated max. working voltage
AC 9.9Vrms, 14V peak value
Number of input channel
3ch
Measuring method
True RMS
RMS measuring interval
approx. 100ms
Sampling interval
Normal/Trigger mode : approx. 1.65ms/CH
Capture mode : approx. 0.55ms (waveform: at every 1.1ms)
Low battery warning
Battery mark display (in 4 levels)
Over-range indication
“OL” mark is displayed when exceeding the measuring range
Auto power off
Power-off function operates automatically after a switch remains for 3min. (when recording is stopped)
Possible measurement time
Approx. 10 days (with alkaline LR6 batteries)
Applicable standards
IEC 61010-1:2001 CAT III 300V Pollution degree2
IEC 61326 (EMC standard)
Dimensions
111(L)×60(W)×42(D)mm
Weight
Approx. 265g
Included Accessories
Alkaline battery LR6×4pcs, 9118 (Carrying case)
PC software “KEW LOG Soft 2”, 7148 (USB cable)
Instruction manual, Quick manual, Install manual,
USB Notice sheet
Optional Accessories
8146/8147/8148 (Leakage & Load current Clamp Sensor),
8121/8122/8123 (Load current Clamp Sensor),
8129/8130 (Flexible Clamp Sensor),
8320 (AC Adapter),
9135 (Carrying bag), 9119 (Hard carry case),
7185 (Extension cable for sensor)