Product Description
Functions
Phase rotation (Clockwise or Counter Clockwise),
Presence of open phase
Detection method
Electrostatic induction
Measuring voltage range
From 70 to 1000V AC phase to phase (sine wave, continuous input)
Clamp diameter range
From Ø2.4 to 30mm insulated cables
Measuring frequency range
Measuring frequency
Phase rotation
Clockwise:Green arrow LEDs “rotate” in clockwise, Green symbol “CW” lits, Intermittent buzzer
Counter Clockwise:Red arrow LEDs “rotate” in counter clockwise, Red symbol “CCW” lits, continuous buzzer
Visual indication
Via LEDs with Super brightness function
Battery voltage warning
Power LED blinks if battery voltage is too low.
Test leads
Double insulated cables, length approx. 70cm
Colours code
L1(U): RedL2(V): WhiteL3(W): Blue
Applicable standards
IEC 61010-1 CAT IV 600V, CAT III 1000V Pollution degree2,
IEC 61326-1, IEC 61557-1, -7
Operating temperature & humidity range
Temperature/Humidity Ranges -10 to 50ºC, 80% (no condensation)
Storage temperature & humidity range
Temperature/Humidity Ranges -20 to 60ºC, 80% (no condensation)
Power supply (DC battery)
Alkaline battery (LR6) ×4
* Continuous use: Approx. 100 hours (Auto power off in about 10 min.)
Dimensions
112(L) × 61(W) × 36(D) mm
Weight
380g approx.
Included Accessories
9096 (Carrying case), Alkaline battery (LR6) × 4, Instruction manual